8. PARAMETER DESCRIPTION
8-88 IMR02C15-E4
To display F21 and after, setting ModE (Mode selection [no display]) in F00 to 128 is required.
(Refer to P. 8-52)
Function block 21 (F21)
This is the first parameter symbol of Function block 21 (F21).
F21
Input type
Data range: 0 to 38 (refer to the following table)
The Input type can be changed. Inputs are selectable within each group
(TC/RTD input group, Voltage/Current input group).
Data range Factory set value
0: TC input K
1: TC input K
2: TC input K
3: TC input J
4: TC input J
5: TC input T
6: TC input T
8: TC input S
9: TC input R
10: TC input E
11: TC input B
12: TC input N
13: TC input PLII
14: TC input W5Re/W26Re
15: RTD input Pt100
16: RTD input JPt100
17: TC input K
18: TC input K
19: TC input J
20: TC input J
21: TC input T
22: TC input T
23: TC input T
24: TC input S
25: TC input R
26: TC input E
27: TC input B
28: TC input N
29: TC input PLII
30: TC input W5Re/W26Re
31: RTD input Pt100
−199.9 to +400.0 °C
0.0 to 800.0 °C
−200 to +1372 °C
−199.9 to +300.0 °C
−200 to +1200 °C
−199.9 to +300.0 °C
0.0 to 400.0 °C
0 to 1769 °C
0 to 1769 °C
0 to 1000 °C
0 to 1820 °C
0 to 1300 °C
0 to 1390 °C
0 to 2320 °C
−199.9 to +649.0 °C
−199.9 to +649.0 °C
−100.0 to +752.0 °F
−328 to +2501 °F
−199.9 to +555.0 °F
−328 to +2192 °F
−199.9 to +300.0 °F
0.0 to 600.0 °F
−328 to +752 °F
0 to 3216 °F
0 to 3216 °F
0 to 1832 °F
0 to 3308 °F
0 to 2372 °F
0 to 2534 °F
0 to 4208 °F
−199.9 to +900.0 °F
Based on
model code
Do not set to any number which is not described in the input range
table above. This may cause malfunction.
Continued on the next page.
F21.