6. OPERATIONS OF THE BASIC FUNCTIONS
IMR02C15-E4
6-13
Startup tuning (ST) setting
The setting procedure when executing Startup tuning (ST) only one time at power ON is shown
below as a setting example.
Set the ST start condition
First, set “When the power is turn on” to ST start condition by Engineering mode.
1. Change the operation mode from RUN mode to STOP mode.
Press and hold the key for 2 seconds or more at the PV/SV monitor screen, then instrument
will go to RUN mode from STOP mode.
To change from RUN mode to STOP mode, refer to 6.1 RUN/STOP Transfer (P. 6-3).
2. Press the key while pressing the key for 4 seconds or more at PV/SV monitor screen
until Engineering mode is displayed. Function block 00 screen is displayed first.
3. Configure settings to display Function block 21 and following of Engineering mode.
Press the key several times until Mode selection (no display) screen will be displayed.
Continued on the next page.
R/S
STOP lamp lights
Output (OUT1) lamp lights
STOP display
PV/SV monitor (RUN mode)
PV/SV monitor (STOP mode)
2 seconds or more
R/S
28
200
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
28
STOP
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
SET
R/S
28$
STOP
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
PV/SV monitor (STOP mode)
Function block 00
(Engineering mode)
F00.
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
4 seconds
or more
R/S
While pressing
the SET key
SET
SET
Mode selection (no display)
(Engineering mode)
MODE
0000
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
Function block 00
(Engineering mode)
F00.
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
SET
Press the key to Mode selection (no display) screen (ModE)
SET