8. PARAMETER DESCRIPTION
IMR02C15-E4
8-67
Dummy
F03
F03 block selection (no display)
Hide parameter symbols of in the Parameter setting mode from the display.
Data range Factory set value
0: Display
1: No display
1
When “No display” is selected, the parameters of Parameter setting mode
are not displayed; however, F03 parameters are displayed.
For details of setting example, refer to 6.7 Display/No display Setting of
Mode Screens (P. 6-32, P. 6-37).
Related parameter
Parameter setting mode:
• Setting change rate limiter (up), Setting change rate limiter (down) (P. 8-18)
Description of function
Hide parameters of the Parameter setting mode from the display. Each parameter of Parameter setting
mode link to the Engineering mode from F01 to F10. The parameters of the Parameter setting mode
linked to the parameters of the Engineering mode is not displayed when “No display” is set to F03
block selection. Those parameters of the Parameter setting mode link to F03 block of the Engineering
mode.
S
.
F03
Engineering mode
Function block 03 (F03)
Setting change rate limiter (up)
Setting change rate limiter (down)
F03 block selection (no display)
Parameter setting mode
Setting change rate limiter (up)
Setting change rate limiter (down)
Not displayed when set to
“1: No display” in
F03 block selection (no display).
Parameter of the F03 block linked
to the Parameter setting mode.