8. PARAMETER DESCRIPTION
IMR02C15-E4
8-119
îš„ Description of function
When an event condition becomes ON, the output is suppressed until the Event timer set time elapses.
If the event output is still ON after time is up, the output will resume.
Example: When the setting of Event 1 timer is 50 seconds
ON
Event state 
Set value (SV) 
Event set value 
Measured value (PV)
Event 1 timer
(50 seconds)
Event output ON 
Event output OFF 
Non-event state 
Event 1 timer
(50 seconds)
DO1 lamp state OFF
The Event timer is also activated for the following reasons:
• When set to the event state simultaneously with power turned on
• When set to the event state simultaneously with control changed to RUN (control start)
from STOP (control stop).
In the event wait state, no event output is turned on even after the Event timer preset time has
elapsed.
The Event timer is reset for the following reasons:
• When power failure occurs while the Event timer is being activated
• When control is changed to STOP (control stop) from RUN (control start) while the Event
timer is being activated

Table of Contents

Other manuals for RKC INSTRUMENT RB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RKC INSTRUMENT RB Series and is the answer not in the manual?

RKC INSTRUMENT RB Series Specifications

General IconGeneral
BrandRKC INSTRUMENT
ModelRB Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals