8. PARAMETER DESCRIPTION
IMR02C15-E4
8-127
Dummy
F51
Control output at burnout
This sets the action when burnout occurs.
Data range Factory set value
0: Result of control computation
1: Low output limiter value (Output OFF) *
* In case of Heat/Cool PID control type both heating
and cooling outputs are off.
0
F51
Bumpless mode setting
This function is used to prevent overload caused by the Manipulated output
value (MV) suddenly changing when Auto mode is transferred to Manual mode
and vice versa.
Data range Factory set value
0: Without bumpless
1: With bumpless
1
Related parameters
Mode switching:
Auto (AUTO)/Manual (MAN) transfer (P. 8-10)
For details of balanceless/bumpless, refer to 6.5 Auto/Manual transfer
(P. 6-20).