Publication 1734-UM001D-EN-P - April 2008
128 Calibrate Your Analog Modules
You see the EDS editor ask you if you want to upload the configuration
from the device.
2. From the EDS editor dialog, click Upload.
3. Click Device Parameters.
You see the Device Parameters dialog.
4. Select Calibration at the Group pull-down.
5. From the Device Parameters dialog, click Calibration Command, and
select Begin Calibration.
Group pull-down