8 | Functions and settings
Page 36 of 104 CIRUS
®
UPT-6400 VERSION 1 | EN-US
8.1.1.2 Configuration
In the Configuration menu, briefly press Menu to advance to the next menu item.
Press Menu for > 2 sec to access the Configuration menu.
The various functions that are available is a factor of whether the timer is activated on
the CIRUS
®
UPT-6400.
Operation menu
Menu
num-
ber
Menu
item
Available
only
when the
timer is
activated
(menu
number
401)
Description Setting range
201 Lan-
guage
Select the desired language.
• German
• English
• French
• Italian
• Dutch
• Spanish
• Swedish
• Polish
• Portuguese
• Finnish
• Danish
• Turkish
• Greek
202 Default Press Enter to reset the temperature controller to the
default; refer to Resetting to defaults [}52].
–
203 Hold
mode
When hold mode is activated, the last value measured at
the end of the heating phase is saved and shown on the
screen.
In the standard screen, ACTUAL (value) is replaced by
HOLD. This process is repeated for each cycle and the
displayed value is updated. HOLD is masked for 100ms
before the update.
When 2 sec is selected, after 2 sec the screen returns
from hold mode to the actual value display in realtime.
Hold mode is not activated for 2 sec again until the end of
the next cycle.
ON
OFF
2 sec
204 Temper-
ature
unit
Unit for temperature display and input
• Celsius
• Fahrenheit
205 AUTO-
CAL but-
ton
Specify here whether AUTOCAL can be started by press-
ing Enter in menu107.
If the button is disabled, AUTOCAL can only be started
via the AUTOCAL signal (terminals 34+39)
• Active
• Disabled