8 | Functions and settings
Page 38 of 104 CIRUS
®
UPT-6400 VERSION 1 | EN-US
Heating element menu
Menu
num-
ber
Menu
item
Available
only
when the
timer is
activated
(menu
number
401)
Description Setting range
301 Temper-
ature co-
efficient
The temperature coefficient can be set to be 1700ppm or
to be variable.
The characteristic curve for the control parameters is cal-
culated on the basis of this setting.
• TCR 1700ppm
• Variable
302 Temper-
ature co-
efficient
If the setting Variable was selected in menu number
301, the temperature coefficient of the heating element
material can be set in this menu item using the Up and
Down buttons.
400…4000 ppm
303 Source
of the
TCR cal-
culator
tempera-
ture
Set how the temperature controller measures the heating
element temperature for the TCR calculator function; re-
fer to section TCR calculator.
Available only when Variable has been selected in
menu number301.
• Internal (value
that the user en-
tered in menu
number 304)
• External (set-
point) (analog in-
put, terminals
36+39)
• External (CH1)
(terminals
39+40)
304 TCR cal-
culator
Available only when Variable has been selected in
menu number301.
Refer to section TCR calculator for further information.
305 Temper-
ature
range
Various temperature ranges can be selected.
The temperature controller is adjusted for the required
temperature by setting the temperature range accord-
ingly. This determines scaling of the progress bar in the
standard screen.
For more information on temperature ranges, refer to
Setting temperature range.
• 200°C
• 300°C
• 400°C
• 500°C
306 Maxi-
mum
tempera-
ture
The maximum setpoint (menu number 101) that can be
chosen within the range defined in menu number305.
100°C to max. tem-
perature range
(menu number 305)
307 Measur-
ing pulse
duration
Change the measuring pulse duration; refer to section
Measuring pulse duration [}81].
1.7…3.0 ms
311 Calibra-
tion
channel
The calibration channels used can be set here.
Refer to section Channel selection (CH0…CH2) [}79]
for further information.
0…7