- 140 -
13.4 Control Parameter Setting Mode
Characters,
Factory Default
Setting Item, Setting Range Data
at//
/ ----
AT Perform/Cancel
---- AT Cancel
AT// AT Perform
pblk
/ ///1
PID block number
1 to 10
p///
1 //10
OUT1 proportional band
Setting range:
Thermocouple, RTD input without decimal point: 0 to input span ( )
Thermocouple, RTD input with decimal point: 0.0 to input span ( )
DC voltage, current inputs: 0.0 to 1000.0%
i///
1 /200
Integral time
Setting range: 0 to 3600 seconds
d///
1 //50
Derivative time
Setting range: 0 to 1800 seconds
arw/
1 //50
ARW
Setting range: 0 to 100%
c///
/ ///3
OUT1 proportional cycle
Setting range: 0.5, 1 to 120 seconds
Available when OUT1 is relay contact output or non-contact voltage output type.
hys/
/ //1.0
OUT1 ON/OFF hysteresis
Setting range:
0.1 to 1000.0 ( )
DC voltage, current inputs: 1 to 10000 (The placement of the decimal
point follows the selection.)
olh/
/ /100
OUT1 high limit
Setting range:
OUT1 low limit to 100%
Direct current output type: OUT1 low limit to 105%
oll/
/ ///0
OUT1 low limit
Setting range:
0% to OUT1 high limit
Direct current output type: -5% to OUT1 high limit
orat
/ ///0
OUT1 rate-of-change
Setting range: 0 to 100 %/sec
cact
/ air/
OUT2 cooling method
air/ Air cooling (Linear characteristics)
oil/ Oil cooling (1.5th power of the linear characteristics)
wat/ Water cooling (2nd power of the linear characteristics)
Available when EV2 option {/020 (Heating/Cooling control output) is selected in
[Event output EV2 allocation]} is ordered, or when DS, DA or EV3D option is
ordered.