[Power Restore Action]
If power fails during program control, the controller can be operated depending on the selection
in [Power restore action].
Progressing time error when power is restored: 1 minute or 1 second
Stops after power is restored:
After power is restored, stops current program control, and returns to Program control STOP
(in Standby) status.
Continues after power is restored:
After power is restored, continues (resumes) program control.
Suspends after power is restored:
After power is restored, suspends (on hold) current program, and performs Fixed value
control using the step SV from the point of suspension.
Pressing the RUN key cancels suspension, and program control resumes.