Connection
4.9 Connecting the IM 154-4 PN High Feature Interface Module with CM IM PN PP Cu
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
101
Pin assignment of push-pull cable connector for 1L+/2L+ and RJ45
View of the push-pull cable connector
Terminal
Assignment
Push-pull cable connector (1L+ and 2L+ supply voltages)
X03 DC 24V for feeding
X04 DC 24V for looping
1
1L+ electronics/encoder supply
2 Ground for electronics/encoder
supply 1M
3
2L+ load voltage supply
4
Ground for load voltage supply 2M
5 Functional earth
Push-pull cable connector (RJ45)
X02 P1 for
connecting
PROFINET
X02 P2 for
connecting
PROFINET
1 Transmit Data+
TD
Receive Data+
RD
2 Transmit Data-
TD_N
Receive Data-
RD_N
3 Receive Data+
RD
Transmit Data+
TD
4
Ground GND
5
Ground GND
6 Receive Data-
RD_N
Transmit Data-
TD_N
7
Ground GND
8
Ground GND
Note
The cable shield support is described in the Hardware Installation Instructions for the push
-
pull cable connector (PROFINET).