EasyManua.ls Logo

Siemens ET 200pro - Page 114

Siemens ET 200pro
545 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection
4.11 Wiring the Electronic Module using the Connection Module
ET 200pro distributed I/O system
114 Operating Instructions, 03/2013, A5E00335544-08
Pin assignment on the CM IO 8 x M8 connection module and the 8 DI DC 24V,
8 DI DC 24V High Feature electronic modules
Table 4- 8 Pin assignment of CM IO 8 x M8 at 8 DI DC 24V, 8 DI DC 24V High Feature
View of circular connector
Terminal
Assignment X1 to X8
1
24V encoder supply U
S
-
-
3
Encoder supply ground 1M
4 Input signal DI
0
: Connector X1
Input signal DI
1
: Connector X2
Input signal DI
2
: Connector X3
Input signal DI
3
: Connector X4
Input signal DI
4
: Connector X5
Input signal DI
5
: Connector X6
Input signal DI
6
: Connector X7
Input signal DI
7
: Connector X8
S (shield)
Functional earth (FE)
Pin assignment on CM IO 8 x M8 connection module and 4 DI / 4 DO DC 24V/0,5A electronic module
Table 4- 9 Pin assignment on CM IO 8 x M8 connection module and
4 DI / 4 DO DC 24V/0.5A
electronic module
View of circular connector
Terminal
Assignment
Terminal
Assignment X1 to X4 (inputs)
1 24 V encoder supply U
S
(from 2L+)
(is supplied by the ET 200pro to the
connected encoder)
3
Ground 2M
4 Input signal DI
0
: Connector X1
Input signal DI
1
: Connector X2
Input signal DI
2
: Connector X3
Input signal DI
3
: Connector X4
S (shield)
Functional earth (FE)
Terminal
Pin assignment X5 to X8 (outputs)
1
Not assigned
3 Ground 2M
4 Output signal DQ
0
: Connector X5
Output signal DQ
1
: Connector X6
Output signal DQ
2
: Connector X7
Output signal DQ
3
: Connector X8
S (shield)
Functional earth (FE)

Table of Contents