Alarm, error and system messages
9.3 LED display on the power, electronic and pneumatic interface modules
ET 200pro distributed I/O system
236 Operating Instructions, 03/2013, A5E00335544-08
Status and error LEDs for the digital electronic modules with the CM IO 4 x M12, CM IO 4 x M12P,
CM IO 4 x M12 Inverse, CM IO 8 x M12, CM IO 8 x M12P, CM IO 8 x M12D, CM IO 8 x M8,
CM IO 2 x M12 and CM IO 1 x M23 connection modules
Table 9- 11 Status and error displays with the digital electronic modules with the connection modules
Status and error
displays
On ---
Incoming diagnostic alarm
Analyze the diagnostic data.
No parameters or faulty parameters
Check the parameter settings.
8 DI DC 24V, 16 DI DC 24V:
On --- Short-circuit at the encoder supply
Check the wiring.
4 DO DC 24V/2.0A, 8 DO DC 24V/0.5A:
Short-circuit at the outputs
On --- Short-circuit Check the wiring of the encoder
Off On (green LED) Input/output at channel X1, X2, X3,
X4, X5, X6, X7 or X8 enabled
---
Off On (green LED) Input on channel X1, X2, X3 or X4
Output on channel X5, X6, X7 or X8
---
8 DI DC 24V High Feature:
On On (red LED) Short-circuit at the encoder supply
1L+
Check the wiring.
Sensor signal line interrupted
Check the wiring and the sensors.
4 DO DC 24V/2.0A High Feature:
On On (red LED)
Short-circuit at the outputs
Load signal line interrupted
Check the wiring and the load.
4 DIO / 4 DO DC 24V/0.5A:
On ---
Incoming diagnostic alarm
Analyze the diagnostic data.
No parameters or faulty parameters
Check the parameter settings.
Short-circuit at the encoder supply
Check the wiring.
Short-circuit at the outputs
Off On (green LED) Input/output enabled at channel X1,
---
Output enabled at channel X5, X6,