EasyManua.ls Logo

Siemens ET 200pro - Page 237

Siemens ET 200pro
545 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Alarm, error and system messages
9.3 LED display on the power, electronic and pneumatic interface modules
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
237
Note
LEDs
The following applies to the digital electronic module 4
DI / 4 DO DC 24V/0.5A:
The inputs DI
0
to DI
3
are displayed with the LEDs 0 to 3 and the outputs DQ
0
to DQ
3
are
displayed with the LEDs 4 to 7.
Status and error LEDs of analog electronic modules with CM IO 4 x M12 connection module
Table 9- 12 Status and error displays of analog electronic modules with CM IO 4 x M12 connection
module
LEDs
Meaning
Remedy
GE
Status and error
displays
On ---
Incoming diagnostic alarm
Analyze the diagnostic data.
No parameters or faulty parameters
Check the parameter settings.
Short-circuit at the encoder supply
1L+
Check the wiring.
Channel fault occurred
---
On On (red LED) Channel fault at the input/output of
channel X1, X2, X3 or X4
---