Analog electronic modules
15.2 Analog electronic module 4 AI I High Feature (6ES7144-4GF00-0AB0)
ET 200pro distributed I/O system
392 Operating Instructions, 03/2013, A5E00335544-08
Dimensions W x H x D (mm)
Rated supply voltage for 1L+ electronics/encoder
Reverse polarity protection
• From backplane bus
Typ. 10 mA
• From electronics/encoder supply 1L+
Typ. 45 mA
Number of encoder supplies
Total current up to 55 °C
Yes, electronic, for each module, to ground
• Response threshold
Min. 1.4 A
Input ranges (rated value)/input resistance
• Current
±20 mA/50 Ω
0 to 20 mA/50 Ω
4 to 20 mA/50 Ω
Permissible current at current input
40 mA
Connection of signal transmitters
• For current measurement
– As 2-wire transducer
– As 4-wire transducer
Yes
Integration time and cycle time/resolution (per channel)
• Integration time can be assigned
Yes
• Interference frequency suppression in Hz
50 60
• Integration time in ms
20 16.667
• Conversion time in ms
66.667 66.667
• Cycle time in ms
(see Appendix Response times)
Number of active channels per module x
conversion time