EasyManua.ls Logo

Siemens ET 200pro - Page 393

Siemens ET 200pro
545 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
15.2 Analog electronic module 4 AI I High Feature (6ES7144-4GF00-0AB0)
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
393
Technical specifications
Resolution (including overrange)
±20 mA/15 bit + sign
0 to 20 mA/15 bit; 14 bit with low-level smoothing.
4 to 20 mA/15 bit; 14 bit with low-level smoothing.
Measured value smoothing
Yes, can be assigned in 4 steps
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
4 x cycle time
16 x cycle time
64 x cycle time
Interference suppression, error limits
Interference voltage suppression for f = n x (f1 ±1 %), (f1 = interference frequency)
Common mode interference (interference
voltage < 5 V)
Min. 70 dB
Series-
mode interference (signal value + peak
value of interference < rated value of input
range)
Min. 50 dB
Crosstalk between inputs
Max. -50 dB
Operational limit (across temperature range,
referenced to input range)
±0.15%
Basic error limit (operational limit at 25 °C,
referenced to input range)
±0.1%
Temperature error (referenced to input range) ±0.002 %/K
Linearity error (referenced to input range)
±0.01%
Repeat accuracy (in steady state at 25 °C,
referenced to input range)
±0.025%
Status, interrupts, diagnostics
Interrupts
Process interrupt (limit value interrupt)
Configurable for channel 0
Diagnostic interrupt
Configurable
Diagnostic functions
Group error display
Red LED (SF)
Channel error display
Yes
Diagnostic functions can be read out
Yes
Monitoring for
Short-circuit to ground (1M)
Yes, at 4 to 20 mA
Wire break
Yes, at 4 to 20 mA
Isolation
Isolation tested with
500 V DC

Table of Contents