Analog electronic modules
15.7 Parameter overview for analog electronic modules
ET 200pro distributed I/O system
426 Operating Instructions, 03/2013, A5E00335544-08
Parameters of analog output modules
Group diagnostics
• Disable
• Enable
Disable Module
Output type —
• Disabled
• Voltage
Voltage Channel
Output range —
• 1 V to 5 V
• ±10 V
• 0 V to 10 V
±10 V Channel
— Output type
• Disabled
• Current
Current Channel
— Output range
• 4 mA to 20 mA
• ±20 mA
• 0 mA to 20 mA
4 mA to 20 mA Channel
Diagnostics of encoder supply short-
circuit to M
1
• Disable
• Enable
Disable Module
Diagnostics of
short-circuit at
---
• Disable
• Enable
Disable Channel
--- Wire break
diagnostics
• Disable
• Enable
Disable Channel
Response to CPU/Master STOP
• Output at zero
current and
zero voltage
• Hold last value
• Output
substitute
values
Output at zero
current and zero
voltage
Module
Substitute value Each value in the
rated and in the
overshoot/undersh
0 Channel
1
Diagnostics of short-circuits of the encoder supply to M is enabled alongside with the group
Overview of parameters of the analog electronic modules (Page 427)