Connection
4.5 Connecting the interface module to a CM IM DP Direct connection module
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
83
Insulate the PROFIBUS DP cables using heat-shrink tubing
1. Cut the piece of heat-shrink tubing included in the CM IM DP Direct package into half.
2. Slide it onto the PROFIBUS Hybrid cable; approximately 7.5
+1
mm of the shielding braid
should remain visible.
3. Shrink the tubing (using a hot-air gun, for example) until it firmly encloses the
PROFIBUS DP cables.
Note
Distribute the heat of your heat source in even movements. Avoid any punctual
overheating of the heat
-shrink tubing.
Figure 4-9 PROFIBUS Hybrid cable with heat-shrink tubing
Result
You can now connect the power supply and PROFIBUS DP cables.
See also
Connecting PROFIBUS DP (Page 84)
Connecting the supply voltages (Page 85)