Connecting the ECOFAST cable connectors
1. Insert the CM IM DP ECOFAST Cu connection module into the interface module.
2. Screw down the CM IM DP ECOFAST Cu connection module to the interface module
(torque = 1.5 Nm). Tighten the four screws evenly, working in cross-wise passes. Those
screws are already attached to CM IM DP ECOFAST Cu connection module.
3. Press down the interlock mechanism of the ECOFAST cable connectors on the
connection module.
4. Plug the ECOFAST cable connectors (1L+, 2L+ and PROFIBUS DP) into the sockets of
the connection module. Observe the mechanical coding of the cable connectors for
feeding and forwarding.
5. Push up the interlock mechanism of the ECOFAST cable connectors.
Figure 4-12 Connecting the ECOFAST cable connectors