4-21
Batch
flexible
, Manual
C79000-G7076-C650-02
A transition contains the step enabling conditions for progress from one step
(AF) to the next. These can be process- and/or time-dependent conditions as
you like. The transition parameters (global variables) which are available
originate in a list of process variables drawn up in the TRANS interface
blocks during the configuration phase (see Technical Data).
Transition:
1
Figure 4-13
T
ransition
The result of a transition condition derives from a boolean expression which
can be formed from a maximum of 10 individual conditions. Each individual
condition is a logic operation with two operands.
The indices of the transitions are numbers which start at ’1’ and which are
unique within the entire recipe. A transition will retain its index until it is
deleted (but this does not result in the indices being renumbered). The
numbers of deleted transitions will be reused once the recipe has been saved.
When generated, the transition has the value TRUE – in other words, batch
control will regard non-parametrized transitions as having been carried out.
If you double-click with the lefthand mouse key on the transition, the
transition dialog will be brought up which you can use to carry out detailed
planning, as described on Page 4-34 onwards.
Transition
Parametrizing
transitions
Recipe creation