User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
channel
-HI-
level,
channel
-LO-
level,
In firmware later than
2.14.2
:
precision
text data describing selected number precision (e.g.: 0.00 mean
two decimal digits),
part data format description
Specific log data. There can be following types of data:
raster
— holds information about samples interval,
Sample ID
in hexadecimal notation
(called:
R
id
),
raster value (in seconds) (called:
R
v
),
timestamp
— samples synchronization markers,
sample ID in hexadecimal notation (called:
T
id
),
sample time (called:
T
t
),
samples
channels measurements data. Channel order is the same as row order
in
log.db_log_files
:
sample ID in hexadecimal notation (called:
S
id
),
floating point text representation of sample value for the first logged channel
floating point text representation of sample value for the N-th logged channel.
How to calculate the precise sample time
To calculate time of sample number
S
id
use below procedure:
Find
R
v
and maximum
R
id
where
R
id
≤ S
id
,
Find
T
t
and maximum
T
id
for
T
id
≤ S
id
,
Calculate sample time (
S
t
) using given equation:
S
t
= T
t
+ R
v
· (S
id
– T
id
)
Detailed description of files
File
main_log.bin_logs
contains:
ID
– unique decimal number identifying log,
GROUP_NO
number of a logged group (correspond to a device's group), starting
from 0,
DIR
name of directory with log files., e.g. “g0_2010_08_04_13_50_39”. The name
of a directory is created according to the schema bellow:
“gX_YYYY_MM_DD_hh_mm_ss”, where:
X
– group number,
YYYY
– year of log start,
MM
– month of log start,
DD
– day of log start,
hh
– hour of log start,
mm
– minute of log start,
ss
– second of log start,