11. System configuration
Pump settings =>Temperature Control => Internal Sensor => External Sensor
Step Key Display Description
Temperature Control
Set internal sensor (controller board) or external sensor
7.1
If internal sensor is enabled:
• Use <down arrow key> to select Temperature Limit
)The following settings are available:
o Over temperature
o Under temperature
• Use <down/up arrow key> to enter the respective values
• Press <Save control key>
• Press <Back control key>
7.2
• Press <OK control key>
)You will enter the External Sensor menu
)The following settings are available:
o disabled
o [transducer 1-6V] [transducer 4-20 mA] [transducer 0-20 mA] [transducer 2-10 V]
[transducer 0-10 V]
o normally closed
o normally open
External Sensor
Sensor Type
[disabled]