NORMAL / NTS STOPPING TEST
1. Move the car to the top landing.
2. Go to your Top Speed Profile speed (S1) in MAIN MENU | SETUP | SPEEDS
& SLOWDOWNS | S1 | S1 DOWN __, record the existing values and
temporarily set the new values to 00001.
a. S1 DOWN Normal Value:__________
b. S1 DOWN Normal Set to 00001. Save this parameter.
3. Enter a call DOWN to a couple of intermediate floors to obtain top speed.
Manual car calls will only work from the MR or CT SRU boards.
4. Observe that car achieves top speed, blows through the called floor and logs
an A64:STOP NO DZ” alarm message. This will confirm that the normal
means of slowdown is disabled.
5. Send the car to the BOTTOM floor and observe that the car stops at the
bottom terminal level. The controller should log a A72:NTS Overspeed”
alarm. This is normal and will confirm the DOWN NTS setting is functioning
properly.
6. Restore the previous recorded S# DOWN Normal parameter from (Step 2a).
7. Go to MAIN MENU | SETUP | SPEEDS & SLOWDOWNS | S1 | S1
SLOWDOWNS | S1 UP__, record the existing value and temporarily set the
new value to 00001.
a. S1 UP Normal Value:__________
b. S1 UP Normal Set to 00001. Save this parameter.
8. With the car at the bottom landing, enter a call UP to a couple of
intermediate floors to obtain top speed. Manual car calls will only work from
the MR or CT SRU boards.
9. Observe that car achieves top speed, blows through the called floor and logs
an A64:STOP NO DZ” alarm message. This will confirm that the normal
means of slowdown is disabled.
10. Send the car to the TOP floor and observe that the car stops at the top
terminal level. The controller should log a A72:NTS Overspeed” alarm. This
is normal and will confirm the UP NTS setting is functioning properly.
11. When testing is complete for the bottom landing restore the previous
recorded S# UP Normal parameter from (Step 7a).