271
ADDENDUM IV PARAMETER ADJUSTMENTS
Binary Parameters
To turn on the options below, go to the MAIN MENU | DEBUG | BINARY PARAMETERS menu
and set any of the following parameters.
Parameter:
OFF
ON
Fire Options:
00-081.4
Smoke 1 to open front door.
Smoke 1 to open rear door.
00-081.5
Smoke 2 to open front door.
Smoke 2 to open rear door.
00-081.6
Smoke 3 to open front door.
Smoke 3 to open rear door.
00-081.7
Smoke 4 to open front door.
Smoke 4 to open rear door.
00-088.5
Fault on Locks Jumped on Fire Phase 2
Bypass Locks Jumped Fault on Fire Phase 2
00-088.6
Main or Remote fire key to override smokes.
Main and Remote Fire key to Override
Smokes
00-088.7
Disable Remote Fire Key
Enable Remote Fire Key
00-106.0
Constant pressure Door Close button
Phase 2 Door Close Button Momentary
00-106.2
Don't Auto-Open at Recall Level
Phase 2 Auto-Open at Recall Level
00-106.7
Lobby Fire Lamp does not flash.
Flash Fire Lobby Lamp when car lamp
flashes (Simplex only)
Fire Code:
00-018.0
New York Fire Code
ANSI Fire Code
00-018.1
New York Fire Code
ANSI Fire Code
00-018.2
N/A
ANSI Fire Code / New York Fire Code
00-018.3
N/A
ANSI Fire Code / New York Fire Code
00-018.4
New York Fire Code
ANSI Fire Code
00-018.5
New York Fire Code
ANSI Fire Code
00-018.6
New York Fire Code
ANSI Fire Code
00-018.7
New York Fire Code
ANSI Fire Code
00-088.5
ANSI Fire Code
New York Fire Code
00-106.3
ANSI Fire Code
New York Fire Code
00-106.6
ANSI Fire Code
New York Fire Code
EMS:
13-014.0
Disable EMS/Code Blue
Enable EMS/Code Blue medical Service
13-014.1
EMT Medical Service
Code Blue medical Service
13-014.2
Phase 1 before Phase 2 Medical
Phase 2 Medical without Phase 1