4) Adjust your valves as required to get proper starts, stops, and run speeds.
There are two parameters that affect the pump motor during starts and
stops.
a. MAIN MENU | SETUP | TIMERS | UP TO SPEED DELAY
i. This parameter allows the pump motor to run for a specified amount
of time at the start of a run before opening the UP valves.
b. MAIN MENU | SETUP | TIMERS | PUMP OFF DELAY
i. This parameter allows the pump motor to continue running for a
specified amount of time at the end of a run after closing the UP
valves.
5) If you’re still experiencing problems running in Construction Mode, use the
following checklist to verify wiring and setup.