MANUEL D’UTILISATION « ASP 116 EVOLUTION »
MAINTENANCE
Sprinte SAS, All rights reserved, including translation rights
77
OOM
OVERCURRENT
The inverter detected a too high value for the measured current
because of an inertia or load too high, or because of a mechanical
locking..
- Check the parameters
- Check the size of the motor/drive/load.
- Check the state of the mechanism.
OOM
GRID OVERVOLTAGE
Power grid voltage is too high or disturbed.
- Check the main power voltage
ALARM
MR SHORT-CIRCUIT
The RM input is short circuited
L’entrée ne passe pas inactive quand l’ascenseur est à l’arrêt.
- Vérifier le câblage de l’entrée E2-CN10-I / 220SP
OO
INVERTER IN ALARM
Frequency inverter in alarm
L’armoire contrôle le bon fonctionnement du variateur
- Vérifier le câblage de l’entrée « E1-CN10-I / 220SP » (si le variateur n’est pas en dialogue
BUSCAN)
- rechercher le défaut sur le variateur de fréquence, initialiser le variateur
OOM
SEE ON INVERTER
This fault is not listed in this controller documentation
- Check directly on the inverter with its terminal.