4-34
02- Motor parameters
02- 00 Motor No Load Current
Range
0~(Patameter 02-01)-0.1】】
02- 01 Motor Rated Current
Range
0.2~100
02- 02 Motor Rated Slip Compensation
Range
0.0 ~ 200.0(%)
02- 03 Motor Rated Speed
Range
0~39000
When the load causes the actual motor speed to be reduced below the speed set by inverter output frequency
(Slip) , parameter 02-02 Slip compensation can be used to correct the speed.
Motor slip= Motor synchronization speed - Motor Rated Speed
Motor synchronization speed (Marked on the motor nameplate)
120
Motor Poles
Motor synchronization speed(RPM)= xMotor rate frequency(50/60Hz)
Note: 02- 00/02- 01 differs with the inverter capacities (13- 00),It should be regulated according to actual
conditions.
02- 04 Motor Rated Voltage
Range
200V: 170.0~264.0 / 400V: 323.0~528.0
02- 05 Motor Rated Power
Range
0.1~37.0
02- 06 Motor Rated Frequency
Range
0~599.0
02- 07 Motor Pole Number
Range
2~ 16
02- 14 Auto Tune
Range
0: Disable
1: Enable
02- 15 Stator Resistance Gain
Range
----
02- 16 Rotor Resistance Gain
Range
----