4-35
In vector mode, selected by parameter 00-00=1, set the motor name plate data in parameters
02-01, 02-03~02-06 then activate the out auto tune function by setting parameter 02-14 = 1.
Auto tune function will set the inverter to run with the specific motor connected to obtain the best
motor performance.
During the Auto tune. “AT” will be displayed on the inverter and there will be an automatic motor
parameter mearurments which will be stored in parameters 02-15~02-16.
After successful auto tune function the display will return to command frequency display.
Auto tune function must be carried out again if the motor is replaced.
03- External Digital Inputs and Relay Output Functions
03- 00 Multifunction Input Term. S1
03- 01 Multifunction Input Term. S2
03- 02 Multifunction Input Term. S3
03- 03 Multifunction Input Term. S4
03- 04 Multifunction Input Term. S5
03- 05 Multifunction Input Term. S6
Range
0:Forward/Stop Command---------------- (Parameters 00- 02/00-03=1& 00-04)
1:Reverse/Stop Command---------------- (Parameters 00- 02/00-03=1& 00-04)
2:Speed Selection 1
3:Speed Selection 2
4:Speed Selection 3
5:Speed Selection 4
6:JOG Forward Command------------( Parameters 00-18~00-20)
7:JOG Reverse Command------------( Parameters 00-18~00-20)
8:Up Command---------( Parameters 00- 05/00- 06=4& 03-06/03-07)
9:Down Command-----( Parameters 00- 05/00- 06=4& 03-06/03-07)
10: 2
nd
Acc/Dec Times
11: Disable Acc/Dec
12: Main/ Alternative Run Source Select----( Parameters 00- 02/00- 03)
13: Main/ Alternative Frequency Command Select----( Parameters 00- 05/00- 06)
14: Rapid Stop (controlled deceleration stop)
15: Base Block (Coast to stop)
16: Disable PID Function ----------( Parameter Goup10)
17: Reset
18: Enable Auto Run Mode-----------( Parameter Goup6)
19: Speed Search
20: Energy Saving(V/F)
21: Reset PID integral value to Zero
22: Counter Input
23: Counter Reset
24: PLC Input
25: Pulse Input-Width Measure (S3)
26: Pulse Input-Frequenct Measure (S3)
27: Enable KEB Function
28:
Fire mode function (Valid for software issued after rev. 1.1 )
Set up examples and descriptions for Parameters 03-00 to 03-05 are noted in the following pages
sections 1 to 13.
1. For setting parameters 03- 00~03- 05 to0, 1External Run/Stop Control, refer to 00- 04.
1A) 2-wire method. Mode 1.
Example: FWD/STOP and REV/STOP from two inputs ( S1&S2)
Set 00- 04=0; S1:03- 00=0(FWD/STOP); S2:03- 01=1(REV/STOP);