4-36
E510
S1
S2
COM
(FWD/STOP)
(REV/STOP)
S1
ON OFF
FWD
REV
ONOFF
S2
Hz
T
Note: If both forward and reverse commands are ON, it will be treated as a STOP.
1B) 2-wire method. Mode 2.
Example: RUN/STOP and REV/FWD from two inputs (S1&S2)
Set 00- 04=1; S1:03- 00=0(RUN/STOP); S2:03- 01=1(REV/FWD);
E510
S1
S2
COM
(RUN /STOP)
(REV/FWD)
S1 ON OFF
FWD
REV
S2
T
Hz
ON
OFF
1C) 3-wire method.
Example:- Two separate push buttons for RUN & STOP and two position switch for FWD/ REV
Set 00- 04 =2.( 3 wire control mode), then terminals S1, S2 and S3 are dedicated to this function and
Preset selections for parameters 03-00, 03-01 and 03-02.are not relevant.