4-60
06- 38 Auto_ Run Mode Running Direction6
06- 39 Auto_ Run Mode Running Direction7
06- 40 Auto_ Run Mode Running Direction8
06- 41 Auto_ Run Mode Running Direction9
06- 42 Auto_ Run Mode Running Direction10
06- 43 Auto_ Run Mode Running Direction11
06- 44 Auto_ Run Mode Running Direction12
06- 45 Auto_ Run Mode Running Direction13
06- 46 Auto_ Run Mode Running Direction14
06- 47 Auto_ Run Mode Running Direction15
Range
【0】: STOP 【1】: Forward 【2】: Reverse
Auto Run (sequencer) mode has to be enabled by using one of the multifunctional inputs S1 to S6 and
setting the relevant parameter 03-00 to 03-04 to selection【18】.
Various Auto Run (sequencer) modes can be selected by parameter (06-00) as listed above.
15 Auto Run (sequencer) modes can be selected by parameters (06-01~06-47)
Auto Run frequency commands 1 to 15 are set with Parameters (06-01 ~ 06-15),
Sequence run times are set with parameters (06-17 ~ 06-31)
FWD/REV Direction for each sequence can be set with parameters (06-33 ~ 06-47).
Auto sequence 0, frequency is set from keypad by parameter 05-01, sequence run time and direction
are set by parameters 06-16 and 06-32.
Auto RUN ( Auto Sequencer) examples are shown in the following pages:-
Example 1. Single Cycle (06- 00=1,4)
The inverter will run for a single full cycle based on the specified number of sequences, then it will stop. In
this example 4 sequences are set, three in forward direction and one in Reverse.
.Auto Run Mode 06- 00=【1】(or【4】),
Frequency 05-01=【15】 Hz, 06- 01=【30】Hz, 06- 02=【50】Hz, 06- 03=【20】Hz
Sequence Run Time 06-16=【20】s, 06-17=【25】s, 06-18=【30】s 06-19=【40】s,
Direction 06-32=【1】, 06-33=【1】, 06-34=【1】(FWD), 06-35=【2】(REV),
Unused Sequence Parameters 06-04~ 06-15=
【0】Hz, 06-20~06-31=【0】s,06-36~06-47=【0】
05-01
06-01
06-02
06-03
06-16
06-17
06-18
06-19
T
Hz
RUN
command
RUN
ON
S1 to S6 auto
run enable