4-61
Example 2: Periodic Cycle Run.
Mode: 06- 00=【2】or【5】
The inverter will repeat the same cycle periodically.
All other Parameters are set same as Example 1. shown above
05-01
06-01
06-02
06-03
05-01
06-01
06-02
06-03
06-16 06-17 06-18
06-19
06-16
06-17
06-18
06-19
T
Hz
RUN
Command
RUN
ON
S1 to S6 auto
Run enable
Example 3. Auto_Run Mode for Single Cycle 06-00=【3 or 6】
The speed of final step will be held to run.
Auto Run Mode 06- 00 = 【3】(or【6】),
Frequency 05- 01=【15】Hz, 06- 01=【30】Hz, 06- 02=【50】Hz, 06- 15=【20】Hz,
Sequence Run Time 06-16=【20】s, 06-17=【25】s, 06-18=【30】s, 06-31=【40】s,
Direction 06-32=【1】, 06-33=【1】, 06-34 = 【1】, 06-47=【1】(FWD),
Unused Sequence Parameters 06-04~06- 15=【0】Hz ,06-19~06-30=【0】s ,06-35~06-46 = 【0】
05-01
06-01
06-02
06-16 06-17 06-18 06-31
Hz
06-15
T
RUN
Command
RUN
RUN
S1 to S6 auto run
enable
Example 4&5 .
Auto_Run Mode 06-00=【1~3】. After a restart, it continues to run from the unfinished step.
Auto_Run Mode 6- 00=【4~6】. After a restart, it will begin a new cycle.