Setting DIP Switch Addresses
BMTW-SVN01F-EN 221
Table 38. DIP Switch Settings for UCMs Supported by Tracer Summit
Device Type Active Range Base
Active Switch Value at Label #:
1 2 3 4 5 6 7 8
Tracer Summit
BCU ID OFF1–7901248163264128
BCU ARCNET OFF1–7901248163264128
Workstation
ARCNET
OFF80–22501248163264128
CSC on1–310168421
LCP on82–12601248163264128
LCP Supervisor on0–8101248163264128
PCM OFF1–30012481632OFFOFF
CGA-CGW on33–6332168421
TCM OFF1–20012481632con-
figure
con-
figure
TRS open0–1501238not
used
con-
figure
not
used
not
used
TUC on33–9601286432168421
UCP1 OFF 1–3 0 on on on 2 1
Universal PCM on32—10001248163264OFF
VAV I OFF1–63012481632
VAV II/III/IV OFF65–1276412481632
VAV wireless
receiver
OFF1–310124816ononcon-
figure
Van Trac II CCP-S2
Voyager
Central Control Panel (CCP)
VAV II/III/IV OFF1–16 012481632
Voyager Micro
Rooftop
on 31 0 con-
figure
on on on on on

Table of Contents

Other manuals for Trane Tracer MP581/AH541

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer MP581/AH541 and is the answer not in the manual?

Trane Tracer MP581/AH541 Specifications

General IconGeneral
BrandTrane
ModelTracer MP581/AH541
CategoryControl Systems
LanguageEnglish

Related product manuals