Chapter 4 UCM Communication-Link Wiring
58 BMTW-SVN01F-EN
Figure 26. Branch Configuration for UCM Communication-Link Wiring
Figure Note:
Maximum wire length for the entire configuration is limited to 5,000 ft
(1,524 m).
The maximum number of branches is 10. There are 6 branches shown in the
figure above. (Comm5 wire connections to a sensor are not considered to be
branches.)
This is not considered a recommended wiring topology for Comm5.
See “Termination Resistance Placement for Comm5 Links.