Teamwork Mode
Teamwork 3 mode was set when the solution was implemented. This mode indicates three functions: Standby, Rotation, and
Fan Cascade Control.
Standby Function
When a unit is defined as a standby unit, the unit's fan runs at the default speed of 0%. The standby unit begins to run when a
critical or normal alarm is triggered on the primary unit.
Critical fault alarms
High pressure lock
Low pressure lock
High discharge temperature lock
Low discharge superheat lock
Low pressure sensor fail lock
Compressor drive fail lock
Fan fail alarm (when the alarm handling is set to shut down)
Water underfloor alarm (when the alarm handling is set to shut down)
Power fail alarm
Normal alarms
High discharge temperature alarm
Air flow temperature sensor failure
Air flow loss alarm
Discharge temperature sensor failure
Suction temperature sensor failure
Low pressure sensor failure
EEV drive communication failure
Compressor drive communication failure
Compressor temperature control sensors failure
Fan temperature control sensors failure
High supply temperature alarm
High return temperature alarm
High remote temperature alarm
RotationFunction
This function ensures that all units have equal runtime. The rotation is preset once every 24 hours.
FanCascade Control Function
This function ensures that a standby unit will start to run if an alarm is triggered on the primary unit, if it was not activated by
system setup.
66 Proprietary and Confidential ©2024 Vertiv Group Corp. 7 Network Settings
Vertiv™ SmartRow™ 2 Infrastructure Solution User Guide