Teamwork Mode
Teamwork 3 mode was set when the solution was implemented. This mode indicates three functions: Standby, Rotation, and
Fan Cascade Control.
Standby Function
When a unit is defined as a standby unit, the unit's fan runs at the default speed of 0%. The standby unit begins to run when a
critical or normal alarm is triggered on the primary unit.
Critical fault alarms
• High pressure lock
• Low pressure lock
• High discharge temperature lock
• Low discharge superheat lock
• Low pressure sensor fail lock
• Compressor drive fail lock
• Fan fail alarm (when the alarm handling is set to shut down)
• Water underfloor alarm (when the alarm handling is set to shut down)
• Power fail alarm
Normal alarms
• High discharge temperature alarm
• Air flow temperature sensor failure
• Air flow loss alarm
• Discharge temperature sensor failure
• Suction temperature sensor failure
• Low pressure sensor failure
• EEV drive communication failure
• Compressor drive communication failure
• Compressor temperature control sensors failure
• Fan temperature control sensors failure
• High supply temperature alarm
• High return temperature alarm
• High remote temperature alarm
RotationFunction
This function ensures that all units have equal runtime. The rotation is preset once every 24 hours.
FanCascade Control Function
This function ensures that a standby unit will start to run if an alarm is triggered on the primary unit, if it was not activated by
system setup.