448 Appendix WAGO-I/O-SYSTEM 750
750-8208 PFC200 CS 2ETH RS CAN DPM
Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
Table 327: Description of Configuration Scripts for “SNMP”
Add new v3-
User
write
config_snmp
v3-edit=add
v3-auth-
name=<Value1>
v3-auth-type=<Value2>
v3-auth-key=<Value3>
v3-privacy=<Value4>
v3-privacy-
key=<Value5>
v3-notification-
receiver=<Value6>
v3-auth-name: User name, string
without spaces, maximum of 32
characters. This must be a new,
unique user name.
Parameters:
User name (<Value1> = string)
Encryption method. (<Value2>
= none, MD5 or SHA).
Key string for authentication,
(<Value3> = String with at least
eight and a maximum of 32
characters)
Privacy encryption method
(<Value4> = none, DES or
AES).
Privacy key string (<Value5> =
String with at least eight and a
maximum of 32 characters), can
also be blank; in this case the
authentication key will be used.
The IP address of a trap receiver
is transmitted as the notification
receiver (<Value6> =
number.number.number.number)
. This parameter is not required if
no v3 traps are to be sent.
After
restart
Delete v3 user write
config_snmp
v3-edit=delete
v3-auth-name=<Value>
Deleting a v3 user that has been
set up.
Because the doubled allocation
of the same user name is
prevented when creating a user,
the name is sufficient to uniquely
identify a data set (<Value> =
After
restart
15.2.1.10 WagoLibCpuUsage.lib
The controller 750-8208supports the following function blocks of the
“WagoLibCpuUsage.lib” library:
- CPU_Usage
The document containing the description of the library and the function block it
includes is available for download on the Internet at www.wago.com.
15.2.1.11 WagoLibDiagnosticIDs.lib
The controller 750-8208supports the following function blocks of the
“WagoLibDiagnosticIDs.lib” library:
- DIAGNOSTIC_SEND_ID
- DIAGNOSTIC_SET_TEXT_FOR_ID