Watlow F4T 124 Chapter 5 Function Reference
TRU-TUNE
+
Band
Set the range, centered on the set point, within which TRU-TUNE+ is in effect. This parameter
applies when TRU-TUNE+ is enabled.
Use this function only if the controller is unable to adaptive tune automatically.
Range: 0 to 100
TRU-TUNE
+
Gain
Set the desired responsiveness of the TRU-TUNE+ adaptive control algorithm. This parameter
applies when TRU-TUNE+ is enabled.
The settings ranging from 1 (least aggressive response and least potential overshoot, low-
est gain) to 6, (most aggressive response and most potential for overshoot, highest gain). The
default setting, 3, is recommended for loops with thermocouple feedback and moderate re-
sponse and overshoot potential.
Range: 1 to 6
Disable TRU-TUNE
®
+ Active Level
Choose the signal value at the TDA receiver which disables TRU-TUNE+.
Options:
High: TRU-TUNE+ is disabled when the signal is on
Low: TRU-TUNE+ is disabled when the signal is off
Control Mode
Choose the method the control loop uses to set power outputs HT, CL and PWR.
Options:
Off: power outputs are 0%
Auto: closed-loop control, the loop adjusts the outputs automatically to make the Pro-
cess Value equal to the Set Point
Manual: open-loop control, the loop’s power outputs are set according to the Manual
Power setting
Note:
When a PID loop's Control Mode is changed from Manual to Auto. The Manual Power is set
equal to the integral value for a bumpless transition and normal PID action takes over to
control to the Set Point.
Control Mode Active
Displays the current method the control loop is using to set power outputs HT, CL and PWR.
Options:
Off: power outputs are 0%
Auto: closed-loop control, the loop adjusts the outputs automatically to make the Pro-
cess Value equal to the Set Point
Manual: open-loop control, the loop’s power outputs are set according to the Manual
Power setting

Table of Contents

Other manuals for Watlow F4T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watlow F4T and is the answer not in the manual?

Watlow F4T Specifications

General IconGeneral
InputsThermocouple, RTD, mA, V
OutputsRelay, SSR, mA, V
CommunicationEthernet, Modbus RTU
Data LoggingYes
CertificationsCE, UL, cUL, RoHS
Control ModesPID, On/Off
Power Supply100 to 240 VAC
Operating Temperature0 to 50°C
Enclosure RatingIP65
Display4.3 in. (109 mm) color touch panel LCD
Control LoopsUp to 4