Watlow F4T 214 Chapter 5 Function Reference
Units
Set the units for the functions output.
Options:
Power: the output is a percentage with 100% representing full power and 0% represent-
ing no power.
Process: the output is in units of measure other than degrees Fahrenheit, degrees Cel-
sius or relative humidity.
Relative Humidity: the output is a measurement of percent relative humidity (%RH).
Absolute Temperature: the output is a temperature on the Celsius or Fahrenheit scale.
Scale Low
Set the electrical signal level at which the Range Low setting is the desired indicated process
value. Scale Low and Range Low are the coordinates of a point on the line that relates the
electrical signal to the conditioned process value produced by this block. Consult the hard-
ware specifications for the signal range supported by the specific hardware.
Use to set the minimum value of the process range in electrical units.
Range: -100.0 to 1000.0 VDC
-100.0 to 1000.0 mVDC
Scale High
Set the electrical signal level at which the Range High setting is the desired indicated process
value. Scale High and Range High are the coordinates of a point on the line that relates the
electrical signal to the conditioned process value produced by this block. Consult the hard-
ware specifications for the signal range supported by the specific hardware.
Use to set maximum value of the process range in electrical units.
Range: -100.0 to 1000.0 VDC
-100.0 to 1000.0 mVDC
Range Low
Set the process value to be indicated when the electrical signal is equal to the Scale Low
setting. Scale Low and Range Low are the coordinates of a point on the line that relates the
electrical signal to the conditioned process value produced by this block.
Use to set the minimum value in process units.
Range: -99,999.000 to 99,999.000°F or units
-55,555 to 55,555°C
Range High
Set the process value to be indicated when the electrical signal is equal to the Scale High set-
ting. Scale High and Range High are the coordinates of a point on the line that relates the
electrical signal to the conditioned process value produced by this block.
Use to set the maximum value in process units.
Range: -99,999.000 to 99,999.000°F or units
-55,555 to 55,555°C