Watlow F4T 226 Chapter 6 Appendix
Parameter Class
and Name
Range Default
Data Type and
Attributes
Modbus Registers
Delay Time 0 To 9999 seconds 0
"unsigned 16-bit
Access=RW"
"Alarm 1: 1348
Alarm n: 1348+((n-1)*
100)"
Output Value
"On (63)
Off (62)"
"unsigned 16-bit
Access = R"
"Alarm 1: 1350
Alarm n: 1350+((n-1)*
100)"
Clear Alarm
"Ignore (204)
Clear (129)"
Ignore (204)
"unsigned 16-bit
Access = RW"
"Alarm 1: 1352
Alarm n: 1352+((n-1)*
100)"
Silence Alarm
"Ignore (204)
Silence Alarms (108)"
Ignore (204)
"unsigned 16-bit
Access = RW"
"Alarm 1: 1354
Alarm n: 1354+((n-1)*
100)"
Alarm State
"Startup (88)
None (61)
Blocked (12)
Alarm Low (8)
Alarm High (7)
Error (28)"
"unsigned 16-bit
Access = R"
"Alarm 1: 1356
Alarm n: 1356+((n-1)*
100)"
Alarm Latched
"No (59)
Yes (106)"
"unsigned 16-bit
Access = R"
"Alarm 1: 1358
Alarm n: 1358+((n-1)*
100)"
Alarm Silenced
"No (59)
Yes (106)"
"unsigned 16-bit
Access = R"
"Alarm 1: 1360
Alarm n: 1360+((n-1)*
100)"
Alarm Clearable
"No (59)
Yes (106)"
"unsigned 16-bit
Access = R"
"Alarm 1: 1362
Alarm n: 1362+((n-1)*
100)"
Alarm Working Process
Value
-99,999.000 to 99,999.000°F
or units, -55,572.778 to
55,537.222°C
"IEEE Float
Access=R"
"Alarm 1: 1370
Alarm n: 1370+((n-1)*
100)"
Source Value B
-99,999.000 to 99,999.000°F
or units, -55,572.778 to
55,537.222°C
"IEEE Float
Access=R "
"Alarm 1: 1378
Alarm n: 1378+((n-1)*
100)"
Source Value C
"On (63)
Off (62)"
"unsigned 16-bit
Access = R"
"Alarm 1: 1386
Alarm n: 1386+((n-1)*
100)"
Silence Active Level
"High (37)
Low (53)"
High (37)
"unsigned 16-bit
Access = RW"
"Alarm 1: 1388
Alarm n: 1388+((n-1)*
100)"
Source Value D
"On (63)
Off (62)"
"unsigned 16-bit
Access = R"
"Alarm 1: 1396
Alarm n: 1396+((n-1)*
100)"
Clear Active Level
"High (37)
Low (53)"
High (37)
"unsigned 16-bit
Access = RW"
"Alarm 1: 1398
Alarm n: 1398+((n-1)*
100)"
Source Value E
"On (63)
Off (62)"
"unsigned 16-bit
Access = R"
"Alarm 1: 1406
Alarm n: 1406+((n-1)*
100)"
Off Active Level
"High (37)
Low (53)"
High (37)
"unsigned 16-bit
Access = RW"
"Alarm 1: 1408
Alarm n: 1408+((n-1)*
100)"