Watlow F4T 238 Chapter 6 Appendix
Parameter Class
and Name
Range Default
Data Type and
Attributes
Modbus Registers
Tolerance 0 To 99999 0.1
"IEEE Float
Access=RW"
"Compare 1: 4830
Compare n: 4830+((n-
1)* 40)"
Error Handling
"True Good (1476)
True Bad (1477)
False Good (1478)
False Bad (1479)"
False Bad (1479)
"unsigned 16-bit
Access = RW"
"Compare 1: 4832
Compare n: 4832+((n-
1)* 40)"
Error
"None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Calibration Data
(139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)"
"unsigned 16-bit
Access = R"
"Compare 1: 4834
Compare n: 4834+((n-
1)* 40)"
Counter (See: p.125)
Source Value A
"On (63)
Off (62)"
"unsigned 16-bit
Access = R "
"Counter 1: 5462
Counter n: 5462+((n-
1)* 50)"
Source Value B
"On (63)
Off (62)"
"unsigned 16-bit
Access = R "
"Counter 1: 5464
Counter n: 5464+((n-
1)* 50)"
Function
"Up (1456)
Down (1457)"
Up (1456)
"unsigned 16-bit
Access = RW"
"Counter 1: 5466
Counter n: 5466+((n-
1)* 50)"
Output Value
"On (63)
Off (62)"
"unsigned 16-bit
Access = R"
"Counter 1: 5468
Counter n: 5468+((n-
1)* 50)"
Count Active Level
"High (37)
Low (53)
Both (13)"
High (37)
"unsigned 16-bit
Access = RW"
"Counter 1: 5470
Counter n: 5470+((n-
1)* 50)"
Reset Active Level
"High (37)
Low (53)"
High (37)
"unsigned 16-bit
Access = RW"
"Counter 1: 5472
Counter n: 5472+((n-
1)* 50)"
Load Value 0 To 9999 0
"unsigned 16-bit
Access=RW"
"Counter 1: 5474
Counter n: 5474+((n-
1)* 50)"
Target Value 0 To 9999 9999
"unsigned 16-bit
Access=RW"
"Counter 1: 5476
Counter n: 5476+((n-
1)* 50)"
Count 0 To 9999
"unsigned 16-bit
Access=R"
"Counter 1: 5478
Counter n: 5478+((n-
1)* 50)"