Watlow F4T • 250 • Chapter 6 Appendix
Parameter Class
and Name
Range Default
Data Type and
Attributes
Modbus Registers
Output Point 8
'-99,999.000 to
99,999.000°F or units,
-55,572.778 to 55,537.222°C
7.0°F or units, -13.9°C
"IEEE Float
Access=RW"
"Linearization 1: 11648
Linearization n:
11648+((n-1)* 70)"
Output Point 9
'-99,999.000 to
99,999.000°F or units,
-55,572.778 to 55,537.222°C
'8.0°F or units,
-13.3°C
"IEEE Float
Access=RW"
"Linearization 1: 11650
Linearization n:
11650+((n-1)* 70)"
Output Point 10
'-99,999.000 to
99,999.000°F or units,
-55,572.778 to 55,537.222°C
'9.0°F or units,
-12.8°C
"IEEE Float
Access=RW"
"Linearization 1: 11652
Linearization n:
11652+((n-1)* 70)"
Error
"None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Calibration Data
(139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)"
- - - -
"unsigned 16-bit
Access = R"
"Linearization 1: 11654
Linearization n:
11654+((n-1)* 70)"
Units
"Source (1539)
None (61)
Absolute Temperature
(1540)
Relative Temperature
(1541)
Power (73)
Process (75)
Relative Humidity
(1538)"
Source (1539)
"unsigned 16-bit
Access = RW"
"Linearization 1: 11656
Linearization n:
11656+((n-1)* 70)"
Math (See: p.147)
Source Value A
-99,999.000 to
99,999.000°F or units,
-55,572.8 to 55,537.2°C
- - - -
"IEEE Float
Access=R "
"Math 1: 12190
Math n: 12190+((n-1)*
80)"
Source Value B
-99,999.000 to
99,999.000°F or units,
-55,572.8 to 55,537.2°C
- - - -
"IEEE Float
Access=R "
"Math 1: 12192
Math n: 12192+((n-1)*
80)"
Source Value C
-99,999.000 to
99,999.000°F or units,
-55,572.8 to 55,537.2°C
- - - -
"IEEE Float
Access=R "
"Math 1: 12194
Math n: 12194+((n-1)*
80)"
Source Value D
-99,999.000 to
99,999.000°F or units,
-55,572.8 to 55,537.2°C
- - - -
"IEEE Float
Access=R "
"Math 1: 12196
Math n: 12196+((n-1)*
80)"
Source Value E
"On (63)
Off (62)"
- - - -
"unsigned 16-bit
Access = R"
"Math 1: 12198
Math n: 12198+((n-1)*
80)"