Watlow F4T • 256 • Chapter 6 Appendix
Parameter Class
and Name
Range Default
Data Type and
Attributes
Modbus Registers
Input A Turn Off -100 To 100% 5
"IEEE Float
Access=RW"
"Special Output
Function 1: 14732
Special Output
Function n: 14732+((n-
1)* 80)"
Input B Turn On -100 To 100% 0
"IEEE Float
Access=RW"
"Special Output
Function 1: 14734
Special Output
Function n: 14734+((n-
1)* 80)"
Input B Turn Off -100 To 100% 5
"IEEE Float
Access=RW"
"Special Output
Function 1: 14736
Special Output
Function n: 14736+((n-
1)* 80)"
Minimum On Time 0 To 9999 seconds 20
"unsigned 16-bit
Access=RW"
"Special Output
Function 1: 14738
Special Output
Function n: 14738+((n-
1)* 80)"
Minimum Off Time 0 To 9999 seconds 20
"unsigned 16-bit
Access=RW"
"Special Output
Function 1: 14740
Special Output
Function n: 14740+((n-
1)* 80)"
Valve Travel Time 10 To 9999 seconds 120
"unsigned 16-bit
Access=RW"
"Special Output
Function 1: 14742
Special Output
Function n: 14742+((n-
1)* 80)"
Dead Band 1 To 100% 2
"IEEE Float
Access=RW"
"Special Output
Function 1: 14744
Special Output
Function n: 14744+((n-
1)* 80)"
Time Delay 0 To 9999 seconds 0
"unsigned 16-bit
Access=RW"
"Special Output
Function 1: 14746
Special Output
Function n: 14746+((n-
1)* 80)"
Output Order
"Linear (1509)
Progressive (1510)"
Linear (1509)
"unsigned 16-bit
Access = RW"
"Special Output
Function 1: 14748
Special Output
Function n: 14748+((n-
1)* 80)"
Output 1 Size 0 To 99999 10
"IEEE Float
Access=RW"
"Special Output
Function 1: 14750
Special Output
Function n: 14750+((n-
1)* 80)"
Output 2 Size 0 To 99999 0
"IEEE Float
Access=RW"
"Special Output
Function 1: 14752
Special Output
Function n: 14752+((n-
1)* 80)"