Watlow F4T 308 Chapter 6 Appendix
Parameter Class
and Name
Range Default
Data Type and
Attributes
Modbus Registers
Message List
Message Enable
"No (59)
Yes (106)"
No (59)
"unsigned 16-bit
Access = RW"
"Message List 1: 37546
Message List n:
37546+((n-1)* 160)"
Message 20 [empty string]
"string
Access=RW"
"Message List 1: 37548
Message List n:
37548+((n-1)* 160)
Read 10 Registers for
20 Characters"
Logging (See: p.54)
Memory Full Action
"Stop (1638)
Overwrite (1639)"
Stop (1638)
"unsigned 16-bit
Access = RW"
42350
Available Logging
Memory (MB)
0 To 4294967295
"unsigned 32-bit
Access=R"
42352
Available Logging
Time (Hours)
0 To 4294967295
"unsigned 32-bit
Access=R"
42354
Source Value A
"Off (62)
On (63)"
"unsigned 16-bit
Access = R"
42362
Logging Status
"Recording (1990)
Not Recording (1991)"
"unsigned 16-bit
Access = R"
42368
File Size Limit (MB) 1 To 4294967295 0
"unsigned 32-bit
Access=RW"
42372
Date Format
"MM/DD/YYYY (1631)
DD/MM/YYYY (1632)"
MM/DD/YYYY (1631)
"unsigned 16-bit
Access = RW"
42382
Time Format
"12 Hour (1966)
24 Hour (1967)"
12 Hour (1966)
"unsigned 16-bit
Access = RW"
42384
Log Action
"None (61)
Start (1782)
Stop (1638)"
"unsigned 16-bit
Access = RW"
42386
Log Interval
"0.1 sec (1971)
0.2 sec (1972)
0.5 sec (1973)
1 sec (1974)
2 sec (1975)
5 sec (1976)
10 sec (1977)
15 sec (1978)
30 sec (1979)
1 min (1980)
2 min (1985)
5 min (1981)
10 min (1986)
15 min (1987)
30 min (1988)
60 min (1989)"
5 min (1981)
"unsigned 16-bit
Access = RW"
42388
Log To
"Internal (2057)
USB Device (2058)"
Internal (2057)
"unsigned 16-bit
Access = RW"
42390
File Type
"Encrypted (2064)
CSV (2063)
Both (13)"
Encrypted (2064)
"unsigned 16-bit
Access = RW"
42392
Create Encrypted
"No (59)
Yes (106)"
No (59)
"unsigned 16-bit
Access = RW"
42394
Encryption Key 0 To 4294967295 Unit's Serial Number
"unsigned 32-bit
Access=RW"
42396

Table of Contents

Other manuals for Watlow F4T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watlow F4T and is the answer not in the manual?

Watlow F4T Specifications

General IconGeneral
InputsThermocouple, RTD, mA, V
OutputsRelay, SSR, mA, V
CommunicationEthernet, Modbus RTU
Data LoggingYes
CertificationsCE, UL, cUL, RoHS
Control ModesPID, On/Off
Power Supply100 to 240 VAC
Operating Temperature0 to 50°C
Enclosure RatingIP65
Display4.3 in. (109 mm) color touch panel LCD
Control LoopsUp to 4