Watlow F4T • 318 • Chapter 6 Appendix
1 Universal Process/Retransmit Output
• Universal process/retransmit, Output range selectable:
- 0 to 10V Î(dc) into a min. 4,000Ω load
- 0 to 20mA into max. 800Ω load
Resolution
- dc ranges: 2.5mV nominal resolution
- mA ranges: 5 µA nominal resolution
Calibration Accuracy
- dc ranges: ±15 mV
- mA ranges: ±30 µA
Temperature Stability
- 100 ppm/°C