3. Next, choose the Operating Mode for the unit. The Operating Modes that appear depend
on the Application chosen in the previous step:
• If Application = SH, or any Application that includes SH, the SH Operating Mode
parameter appears. Choose: Constant Setpoint, Remote Setpoint or Outdoor Temp
Reset.
• If Application = DHW, or any Application that includes DHW, the DHW Operating
Mode parameter appears. Choose either: Constant Setpoint or Remote Setpoint.
• If Application = Other, or any Application that includes Other, the Other
Operating Mode parameter appears. Choose either: Constant Setpoint or
Remote Setpoint.
4. Additional parameters now appear, depending on the combination of Application and
Operating Mode chosen in Steps 2 and 3, and in some cases depending on the value of
another parameter, as shown in the tables below. Descriptions of all parameters appear
below the tables.
* Outdoor Air Reset requires a header temp sensor and an outdoor air temp sensor to be
connected to the one of the units in the cascade, either directly, via the network or BAS.