SECTION 10 – STARTUP, STATUS, FAULT MESSAGES
OMM-139_E • 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 188 of 196
TABLE 10-1: Edge Controller Fault Messages
The Remote Interlock is open.
The Delayed Interlock is open.
Airflow Fault During Purge
The Blower Proof switch opened during purge, or
air inlet is blocked.
The SSOV switch opened dug purge.
Prg Switch Open During Purge
The Purge Position Limit switch on the Air/Fuel
Valve was open during purge.
Ign Switch Open During Ignition
The Ignition Position Limit switch on the Air/Fuel
Valve opened during ignition.
The Blower Proof switch opened during ignition.
The Blower Proof switch opened during run.
SSOV Fault During Ignition
The SSOV switch closed or failed to open during
ignition.
The SSOV switch closed for more than 15
seconds during run.
Flame Loss During Ignition
The Flame signal was not seen during ignition or
lost within 5 seconds after ignition.
The Flame signal was lost during run.
The High Exhaust Temp switch is open.
The unit shut down due to loss of power
The O
2
Sensor reading is above acceptable
level.
The O
2
Sensor reading is below acceptable level.
A failure has been detected in one of the relays
that control the SSOV.
The Flame signal was seen for more than 60
seconds during standby.
The unit failed to fulfill the demand for heat.
Ign Switch Closed During Purge
The Ignition Position Limit switch on the Air/Fuel
Valve closed during purge.
Prg Switch Closed During Ign
The Purge Position Limit switch on the Air/Fuel
Valve was stuck closed during ignition.
The SSOV switch opened during standby.
A communication fault has occurred between the
PMC board and Ignition board.
The unit is waiting for a process to run to
completion.
Direct Drive Signal Fault
The direct drive signal is not present or is out of
range.