Edge [ii] Controller Operation Manual
SECTION 10 – STARTUP, STATUS, FAULT MESSAGES
OMM-139_E • 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 189 of 196
TABLE 10-1: Edge Controller Fault Messages
Remote Setpt Signal Fault
The Remote Setpoint signal is not present or is
out of range.
Outdoor Temp Sensor Fault
The temperature measured by the Outdoor Air
Sensor is out of range.
The temperature measured by the Outlet Sensor
is out of range:
• OUTLET TEMPERATURE display = Sht
Indicates sensor is shorted
• OUTLET TEMPERATURE display = Opn
indicates sensor is open-circuited
The temperature measured by the Feed Forward
(FFWD) Sensor is out of range.
The temperature measured by the Outlet Sensor
exceeded the Temp Hi Limit setting.
Line Voltage Out of Phase
The Line (Hot) and Neutral wires are reversed.
The Stepper Motor failed to move the Air/Fuel
Valve to the desired position.
Outlet temperature crossed the high setpoint
limit. Setpoint limiting feature is active.
A network communication fault
The unit is waiting before retrying to ignite.
Pause before retrial for ignition.
Exhaust Temp Sensor Short
The Exhaust Temp Sensor has malfunctioned.
Exhaust Temp Sensor is not connected or
malfunctioned.
Warning Exhaust Temp High
The Exhaust temperature is above normal.
The Exhaust Temperature has exceeded 200°F
(93.3°C).
Inlet Water Temp Sensor Short
Inlet Water Temp Sensor has
malfunctioned/shorted out.
Inlet Water Temp Sensor Open
Inlet Water Temp Sensor is not connected or
malfunctioned.
Warning: Inlet water temperature is above
normal.
Warning: Inlet water temperature is below
normal.
Inlet Gas Press Sensor Open
Inlet Gas Pressure Sensor is not connected or
malfunctioned.
Gas Plate Dp Sensor is not connected or
malfunctioned.
The O2 % has gone below 2% for more than 30
seconds
Indicates O
2
Levels are less than -4% or more
than 24% for more than 10 seconds.
The O
2
is above normal operating limits.
The recirculation pump has failed.