Edge [ii] Controller Operation Manual
SECTION 10 – STARTUP, STATUS, FAULT MESSAGES
OMM-139_E • 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 190 of 196
TABLE 10-1: Edge Controller Fault Messages
The ignition spark monitor indicated no or out of
range spark.
The O
2
is above normal operating limits.
The recirculation pump has failed.
Displayed during ignition sequence during the
Spark Cleaning cycle.
Too Many Cycles In 24 Hours
The number of cycles experienced by the unit
exceeded the allowable limit.
Too Many Ovrtmps In 24 Hours
The number of over-temperature events
exceeded the allowable limit.
The Air Temp sensor has malfunctioned.
Auto Diagnostic Mode ACTIVE
The unit is in Auto Diagnostic Mode
Auto Diagnostic Mode COMPLETED
Auto Diagnostic Mode has completed
Auto Diagnostic Mode ABORTED
Auto Diagnostic Mode has aborted
The unit is actively heating domestic hot water.
The unit has ceased firing and is now cooling
down.
BST Network Temp Sensor Fault
BST network temp sensor fault.
BST Network Temp Com Fault
BST network temp communication fault.
BST Local Header Sensor Fault
BST local header sensor fault.
BST Net Outdoor Sensor Fault
BST net outdoor sensor fault.
BST Net Outdoor Com Fault
BST net outdoor communication fault.
BST Local Outdr Sensor Fault
BST local outdoor sensor fault.
Communication with a BST Client unit failed.
O
2
calibration is in purge cycle.
Auto Calibration In Progress
O
2
calibration is underway.
O
2
calibration is complete.
O
2
sensor failed during O
2
calibration.
O2 Warning Service Required
AERtrim has reached its limit and O2 level is still
out of range.
The unit is waiting for the O
2
sensor to turn on.
Air Pump Failed O2 Trim Disabled
Air Aductor pump failed, disabling O
2
trim
functionality (BMK5000-6000 only)
onAER Communication failed
onAER communication failed. No internet
connection.
Isolation Valve Stuck Open
The isolation valve failed to close as expected.
Isolation Valve Stuck Closed
The isolation valve failed to open as expected.
Scheduled 12- or 24-month maintenance is
overdue.
Scheduled 12- or 24-month maintenance is due
in near future.
Unit is shut down remotely via BAS