5.17 Resetting the Absolute Encoder
5.17.3 Operating Procedure
5-52
5.17.3
Operating Procedure
Use the following procedure to reset the absolute encoder
1.
Confirm that the servo is OFF.
2.
Select Setup - Reset Absolute Encoder from the menu bar of the Main Window of the
SigmaWin+.
3.
Click the Continue Button.
Click the
Cancel Button to cancel resetting the absolute encoder. The Main Window will return.
4.
Click the Execute setting Button.
The current alarm code and name will be displayed in the Alarm name Box.
5.
Click the Continue Button.
Click the Cancel Button to cancel resetting the absolute encoder. The previous dialog box will return.