13.4 Utility Function (Fn) Operations on the Panel Operator
13.4.7 Reset Absolute Encoder (Fn008)
13-16
13.4.7
Reset Absolute Encoder (Fn008)
Refer to the following section for information on this utility function other than the procedure.
5.17 Resetting the Absolute Encoder on page 5-51
3
Press the DATA/SHIFT Key for approximately one sec-
ond. The display shown at the left will appear.
4
Press the MODE/SET Key to clear the alarm history.
When deleting the alarms has been completed, donE
will flash on the display, and then the display shown on
the left will appear again.
5
Press the DATA/SHIFT Key for approximately one sec-
ond to return the display to Fn006.
Step
Panel Display after
Operation
Keys Operation
Step
Panel Display after
Operation
Keys Operation
1
Press the MODE/SET Key to enter Utility Function
Mode.
2 Press the UP Key or DOWN Key to display Fn008.
3
Press the DATA/SHIFT Key for approximately one
second. PGCL1 will be displayed.
4
Continue pressing the UP Key until PGCL5 is dis-
played.
Note: If you press the wrong key, no-oP will flash
on the display for approximately one sec-
ond and the display will return to the origi-
nal Utility Function Mode display. Repeat
the operation from the beginning.
5
Press the MODE/SET Key.
The absolute encoder will be initialized.
When initialization has been completed, donE will
flash on the display for approximately one second.
6 –
After displaying donE, the display will return to the
PGCL5 display.
7
Press the DATA/SHIFT Key for approximately one
second to return the display to Fn008.
8
To enable the change to the settings, turn the power supply to the SERVOPACK OFF and ON
again.
MODE
SET
DATA
MODE
SET
MODE
SET