4.3 Wiring the Power Supply to the SERVOPACK
4.3.1 Terminal Symbols and Terminal Names
4-11
4
Wiring and Connecting SERVOPACKs
4.3
Wiring the Power Supply to the SERVOPACK
4.3.1
Ter m ina l Sy m bo l s an d Ter min a l Na mes
Use the main circuit connector on the SERVOPACK to wire the main circuit power supply and
control circuit power supply to the SERVOPACK.
The SERVOPACKs have the following three types of main circuit power supply input specifica-
tions.
Three-Phase, 200-VAC Power Supply Input
Single-Phase, 200-VAC Power Supply Input
CAUTION
Wire all connections correctly according to the following table and specified reference infor-
mation. There is a risk of SERVOPACK failure or fire if incorrect wiring is performed.
Ter mi n a l
Symbols
Ter mi n a l Na me Specifications and Reference
L1, L2, L3
Main circuit power supply
input terminals for AC
power supply input
Three-phase, 200 VAC to 240 VAC, -15% to +10%, 50 Hz/60
Hz
L1C, L2C
Control power supply termi-
nals
Single-phase, 200 VAC to 240 VAC, -15% to +10%, 50 Hz/60
Hz
B1/ , B2, B3
Regenerative Resistor termi-
nals
4.3.5 Wiring Regenerative Resistors on page 4-17
For SGD7S-R70A, -R90A, -1R6A, and -2R8A
If the regenerative capacity is insufficient, connect an Exter-
nal Regenerative Resistor between B1/ and B2.
The External Regenerative Resistor is not included. Pur-
chase it separately.
For SGD7S-3R8A, -5R5A, -7R6A, -120A, -180A, and
-200A
If the internal regenerative resistor is insufficient, remove the
lead or short bar between B2 and B3 and connect an Exter-
nal Regenerative Resistor between B1/ and B2.
The External Regenerative Resistor is not included. Pur-
chase it separately.
1, 2
DC Reactor terminals for
power supply harmonic
suppression
4.3.6 Wiring DC Reactors on page 4-18
These terminals are used to connect a DC Reactor for power
supply harmonic suppression or power factor improvement.
None. (Do not connect anything to this terminal.)
Ter mi n a l
Symbols
Ter mi n a l Na me Specifications and Reference
L1, L2
Main circuit power supply
input terminals for AC
power supply input
Single-phase, 200 VAC to 240 VAC, -15% to +10%, 50 Hz/60
Hz
L1C, L2C
Control power supply termi-
nals
Single-phase, 200 VAC to 240 VAC, -15% to +10%, 50 Hz/60
Hz
Continued on next page.